Overview
Vertiv VP4UU0A1 is a Geist input-metered rack power distribution unit for professional IT racks.
Use Cases
- Universal-input rack power for sites standardising on one PDU across supply types
- Vertical (Zero-U side) rack power distribution
- Networked power monitoring
Input Power
- Input: universal inlet; voltage, current and capacity are defined by the facility side cable (ordered separately)
- Maximum input by facility side cable: 48A Single Phase, 240V Max, 11.0kW
- Maximum input by facility side cable: 24A 3 Phase DELTA, 240V Max, 8.6kW
- Maximum input by facility side cable: 16A Three Phase WYE, 240/415V Max, 11.0kW
- Frequency: 50/60Hz
- Plug type: Universal Inlet
- Overcurrent protection: (3) 16A Double Pole Magnetic Breakers (10kAIC Rated)
Outlets & Monitoring
- Outlets: 42 x Combination C13/C19
- Monitoring: Input and per Phase power monitoring with Circuit/Breaker current monitoring. Environmental monitoring via optional remote sensors. Daisy chain Ethernet connectivity. Local high visibility display.
Management & Connectivity
- Network: Dual 10/100/1000Mbps Ethernet
- Protocols: DHCP, HTTP, HTTPS, IPv4, IPv6, LDAP, NTP, RADIUS, RSTP, SSH, SMTP, SNMP (v1/v2c/v3), Syslog, TACACS+, Modbus TCP
- Remote sensor jacks: 1 (Supports up to 16 Sensors)
Physical
- Form: 70in / 1778mm, Vertical
- Mounting: Zero U
- Chassis Dimensions (LxWxD): 70in x 2in x 2.25in / 1778mm x 51mm x 58mm
- Shipped weight: 22lbs (9.98kg)
- Maximum operating temperature: 60C / 140F
Ordering Information
- Exact order code: VP4UU0A1
- Vertiv model configuration: DU05M4W1-42CF17-1S02A9K00-S-A
- The facility side cable (FSC) is a separate order line chosen for the site supply